Product Details:
Payment & Shipping Terms:
|
Rated Capacity: | 1600kVA | Rated Voltage: | 10kV |
---|---|---|---|
Cooling Type: | ONAN/ONAF/OFAF | Name: | Induction Furnace Transformer |
Type: | Core Type/shell Type | Winding Material: | Copper |
Highlight: | electric furnace transformer,arc furnace transformer |
2 / 3 Winding Induction Melting Furnace Single Phase Transformer , 10kV 1600kVA
Quick Detail:
1.Low loss, low noise
2.Low partial discharge
3.High quality,efficiency
4.Safe use
5.power frequency induction furnace transformer
Description:
Furnace transformer is power transformer which is used on industry furnace smelting, it’s a special transformer which is designed according to work principle, lead character and operation characteristic. It contains steel-making arc furnace transformer ladle refining furnace transformer, electro slag furnace transformer, submerged arc furnace transformer(ferroalloy furnace, calcium carbide furnace, phosphorus furnace and so on).all kinds of transformers which are use on alternative current furnace such as power frequency induction furnace transformer.
It has more stringent requirements in electric, magnetic, thermal, mechanical and other aspects compared with other transformers, and has to comply with the operation process of various furnace transformers and load characteristics, so that it can meet users, and facilitate energy-saving emission reduction and other conditions.
There are many kinds of furnace transformers. The company mainly produce the following products:
Features:
1.Wide range of voltage-regulate. Secondary voltage of differential voltage levels meets the arc furnace steel-making process requirements.
2.High-voltage has no restriction of switching insulation level, and it (e.g. 110kV) can be reduced to low-voltage directly, eliminating the intermediate substation and saving more than 30% invested.
3.Easy to choose suitable voltage-level load tap changer, economic and safe.
4.It can be accessed compensation capacitor in order to improve network power factor.
5.The main transformer works in constant flux density. Make full use of materials and have a good conservation.
6.Using the same reverse-phase parallel, electric (or magnetic) shielding, transposed conductors and so on to reduce losses and improve efficiency.
7.A separate voltage coil is used so that ampere-turn balance is good, coupled with cylinder pressure nail structure, its ability to withstand short-circuit is also increased and has high reliability.
8.Using third breaking off instead of primary breaking off so that it can be achieved with low price and high life of low-voltage circuit breakers instead of high price and low life of high-voltage circuit breaks.
Take 31500/110 arc furnace transformer for example, the load loss, no-load loss, no-load current is dropped 13%, 17%, 26% compared with the original product respectively. It is a real energy-saving emission reduction innovative product.
Product model of furnace transformer is made up of bellowing codes:
Use---phase---kinds of cooling device---oil-circulating type---voltage-regulating type---inner contains attached device---rated capacity/voltage class
Use: H- steel-making arc furnace;
HJ- ladle refining furnace;
HZ- electro-slag furnace;
HC- calcium carbide furnace
HT- ferroalloy furnace;
HL- phosphorus furnace
HG- power frequency induction furnace
Phase: D- single phase;
S- three phase
Type of Cooling: “—” ONAN
F- oil-immersed natural air cooling-air cooling
S- water cooling
Type of oil circulating: “—” natural circulation;
P- forced oil circulation
Type of tap changing: “—” off-circuit voltage regulating
Z- on-load tap changing;
Inner contains attached device: “—” change magnetism-leaking group;
K- inner attached reactor
Rated capacity: KVA
Voltage level: KV
Applications:
Power frequency induction furnace transformer is power transformer which is designed according to work principle, lead character and operation characteristic and can be used for steel and non-ferrous metal smelting, extracting various ferroalloys, silicon compounds and extraction of pure silicon.
Specifications:
Power frequency induction furnace transformer
Rated Voltage |
10kV |
Rated Capacity | 1600kVA |
Cooling Type | ONAN/ONAF/OFAF |
Winding Type | Double winding/Three winding/Toroidal |
Phase | Three phase/ Single phase |
Type | Core type/shell type |
Winding Material | Copper |
Frequency | 50Hz/60Hz |
Type |
Rated Capacity (kVA) |
Rated Voltage |
Connection Symbol |
Weight(kg) |
Overall Dimension (mm) L*W*H |
Wheelbase (mm) W*L |
|||
Primary (kv) |
Secondary (v) |
Active Part |
Oil |
Total |
|||||
HGS-630/10 |
630 |
10 |
440`260 254`150 |
D-Y y11-0 |
1580 |
1190 |
3920 |
2500*1150*2000 |
820*820 |
HGS-700/35 |
700 |
35 |
500/480/460 /440/420/400 /370 /340/310 |
Yd11 |
1700 |
1440 |
4320 |
2750*1500*2440 |
820*820 |
HGS-800/10 |
800 |
10 |
1050`520 606`300 |
D-Y y11-0 |
2200 |
1400 |
4400 |
2560*1500*2250 |
820*820 |
HGSZ-1000/10 |
1000 |
10 |
1050/1000/950 /900/850/800/ 750/700/650 |
Dy11 |
2150 |
1300 |
4800 |
2600*1560*2500 |
1070*800 |
HGS-1000/10 |
1000 |
10 |
1050/1000/950 /900/750/625 /500/400/300 |
Ynd11 |
1850 |
940 |
3840 |
2600*2100*2250 |
1070*800 |
HGS-1600/10 |
1600 |
10 |
500/480/460/440/420/400/370 /340/310 |
Yd11 |
2550 |
1500 |
5650 |
2800*1690*2490 |
820*820 |
HGS-1600/10 |
1600 |
10 |
1046`300 |
D-Y y11-0 |
2950 |
1670 |
6200 |
2190*1680*2480 |
820*820 |
HGSZ-1600/10 |
1600 |
10 |
544`270 |
Yd11 |
2800 |
1600 |
6000 |
2750*1760*2540 |
820*820 |
HGS-1600/35 |
1600 |
35 |
500/480/460/440/420/400/370 /340/310 |
Yd11 |
3400 |
2250 |
7500 |
3130*1560*2810 |
1070*1070 |
HGSZ-2000/10 |
2000 |
10 |
480/456/432 /408/360/321 /290/264 |
Yao Yd11 |
3640 |
2040 |
7900 |
2870*1960*2570 |
1070*1070 |
HGSZ-2000/10 |
2000 |
10 |
1030/1000/950 /830/710/590 /470/350/300 |
Yd11 |
4550 |
3000 |
9800 |
2800*2390*2580 |
1070*1505 |
HGS-2500/10 |
2500 |
10 |
1500`520 606`300 |
D-Y y11-0 |
4730 |
2080 |
8000 |
3000*2150*2830 |
1070*1070 |
HGS-3150/10 |
3150 |
10 |
1500`520 606`300 |
D-Y y11-0 |
6330 |
2450 |
10450 |
3000*2260*2860 |
1070*1070 |
HGS-4200/10 |
4200 |
10 |
1500`520 606`300 |
D-Y y11-0 |
7850 |
3000 |
13000 |
3700*2600*3160 |
1505*1505 |
A . Transformers application:
B . Production process:
C . Production Equipments:
D . Packing and Delivery Processing:
E . Quality Certificates:
F . Team Work:
G . FAQ About Transformers:
Q: 1. Are transformers apply with Internation Standrad?
A: Yes, all our product are strictly apply with IEC,IS,ANSI,GB or any other special requirements as customers.
Q: 2. What is the lead time?
A:Generally for one lot transformers within 60-90 days.
Q: 3. How do transformers been shipped?
A: Transformers always been deliveried by ship,train or truck for oversea.Which with main active body in bulk and accessories in wooden cases.
Q: 4. What kind of internation certificates do you have?
A: We have authoried KEMA,ISO and SGS.
Q: 5. What is your production ability for last year?
A: Last year our production ability reach 50 million KVA,and increased every year.
Q: 6. Do you offer guarantee for the products?
A: Yes, we offer at least one year guarantee for all of our transformers.
Q: 8. Do you accept FAT(Factory Acceptance Test)?
A: Yes, it’s available.Welcomed.We are responsible for each set transformer’s testing.
Q: 9. Do you assign engineer for after-sale service?
A: Yes,for our products,we all show after-sale guide installation and questions inquiry.
Contact Person: Mr. zhang
Tel: 18810288990
Fax: 86-189-9086-7684